logo
Thuis ProductenGassensor

YJJ C03-0801-000 Whittle LEL 4R+ Industrial-grade Catalytic Combustion Gas Sensor

Certificaat
CHINA ShenzhenYijiajie Electronic Co., Ltd. certificaten
CHINA ShenzhenYijiajie Electronic Co., Ltd. certificaten
Ik ben online Chatten Nu

YJJ C03-0801-000 Whittle LEL 4R+ Industrial-grade Catalytic Combustion Gas Sensor

YJJ C03-0801-000 Whittle LEL 4R+ Industrial-grade Catalytic Combustion Gas Sensor
YJJ C03-0801-000 Whittle LEL 4R+ Industrial-grade Catalytic Combustion Gas Sensor YJJ C03-0801-000 Whittle LEL 4R+ Industrial-grade Catalytic Combustion Gas Sensor YJJ C03-0801-000 Whittle LEL 4R+ Industrial-grade Catalytic Combustion Gas Sensor YJJ C03-0801-000 Whittle LEL 4R+ Industrial-grade Catalytic Combustion Gas Sensor YJJ C03-0801-000 Whittle LEL 4R+ Industrial-grade Catalytic Combustion Gas Sensor

Grote Afbeelding :  YJJ C03-0801-000 Whittle LEL 4R+ Industrial-grade Catalytic Combustion Gas Sensor

Productdetails:
Plaats van herkomst: Brittannië
Merknaam: YJJ
Modelnummer: C03-0801-000 Whittle LEL 4R+
Betalen & Verzenden Algemene voorwaarden:
Min. bestelaantal: 1
Prijs: Onderhandelbaar
Verpakking Details: Ingeblikt
Levertijd: 5 dagen
Betalingscondities: L/C, D/A, D/P, T/T, Western Union, MoneyGram
Levering vermogen: 2200

YJJ C03-0801-000 Whittle LEL 4R+ Industrial-grade Catalytic Combustion Gas Sensor

beschrijving
Reactietijd T90: <30 seconden Bedrijfsspanning: 4,25V (4R + serie)
Temperatuurbereik: -40℃ ~ +60℃ Vochtigheidsbereik: 5%–95% RV
Levensduur: 2–3 jaar Uitgangssignaal: Analoog
0–100% LEL: Komt overeen Detectieprincipe: Katalytische verbranding
Markeren:

Industrial-grade catalytic combustion gas sensor

,

Whittle LEL 4R+ gas sensor

,

YJJ C03-0801-000 gas detector

Product Description:

YJJ C03-0801-000 Whittle LEL 4R+ Industrial-grade Catalytic Combustion Gas Sensor

 

Features:

I. Core Parameters (Quick Overview)

Detection principle: Catalytic combustion (Whitworth bridge, platinum wire catalytic beads)

Detected gases: Methane, propane, hydrogen, ethane, ethylene, -, ethanol, etc. combustible gases/vapors

Range: 0–100% LEL (covering the conventional explosion lower limit)

Resolution: 1% LEL (industrial standard)

Accuracy: ±3% FS (full scale)

Response time T90: < 30 seconds

Operating voltage: 4.25V (4R + series)

Temperature range: -40℃ ~ +60℃

Humidity range: 5%–95% RH (no condensation)

Life span: 2–3 years (conventional industrial environment)

Output signal: Analog (4R + interface), compatible with BW host

Explosion-proof certification: Ex ia IIC T4, IECEx, CSA, etc.

 

II. Parameter Definitions (Reasons for Such Settings)

0–100% LEL: Corresponds to the entire range from "safe" to "explosive limit", with the alarm set at 10–20% LEL (low alarm) and 50% LEL (high alarm).

−40℃ to +60℃: Suitable for extremely cold / hot industrial sites (such as outdoor areas in the north, refining and chemical plant areas).

4R + analog interface: Specifically for BW, plug-and-play, the host automatically recognizes, compatible with Ultra, GasAlertMax XT II, etc.

Catalytic combustion: Has good linearity for most combustible gases and a moderate cost; but avoids silicon / sulfur / lead poisoning (such as when using silicon oil or in environments with high concentrations of hydrogen sulfide, filtering is required).

 

III. Main Applications (Industry Scenarios)

1) Petroleum and Petrochemical (Core)

Refineries, oil and gas extraction platforms, storage tank areas, pipeline valves, compressor rooms leakage monitoring.

LNG/CNG refueling stations, pressure regulating stations, explosion-proof warning for transportation pipelines.

2) Chemicals / - / Paints

Reaction vats, solvent warehouses, spray painting rooms, RTO exhaust gas treatment front end (explosion-proof).

Organic solvent (ethanol, -, ethyl acetate) concentration monitoring in pharmaceutical / pesticide workshops.

3) Gas and Energy

Urban gas ** pipeline network inspection, boiler rooms, gas meter rooms, kitchens (commercial)** leakage alarm.

Coal mine methane (methane) monitoring, detection before entering tunnels / underground confined spaces.

4) Industrial Safety and Confined Spaces

Wastewater treatment plant methane (methane), landfill gas monitoring.

Ship cabins, storage tanks, sewers, reaction vats confined space operations (test first, then enter).

Portable detectors (such as BW GasAlert), core sensing components, for inspection / emergency.

 

Specifications:

Detected gases Methane, propane
Range 0-100% LEL
Resolution 1% LEL
Accuracy ±3% FS (full scale)
Sensitivity 450-750 na/PPM
Response time T90 < 30 seconds

 